POWER QUALITY ANALYSER AND DATA LOGGER RPM-416

Product Details:

Input TypeAC Voltage, AC Current, Temperature, Analogue Transducer, Dry contact
Voltage (V)24 – 265V AC/DC
Number of Inputs15 input channels (Sampling – 1 millisec to 3600 sec programmable)
ApplicationContinuous Power Quality Analysis and Data Logging
Channels3 x Voltage, 4 x Current, 2 x Temperature, 2 x Analogue, 4 x Dry contacts
Memory32 GB external SD/MMC
AdditionalBuilt-in Ethernet port, Free PC software for analysis and report generation
BrandNOVATEK ELECTRO

 

Power Analyser and Data logger RPM-416 is a device intended for power quality analysis, electrical & process parameters measuring, monitoring as well as data archiving/storage with a sampling rate starting from 1 millisecond.

– Data sampling rate 1 msec – 3600 sec.

– Data archiving is made on the removable memory card (SD/MMC), which can be later analyzed in free PC software program provided with the logger.

– RPM-416 has an inbuilt real time clock powered by internal lithium-type battery.

– Device can be connected to Ethernet network via standard 10Base-T or 100Base-T. Data transfer happens simultaneously with data recording to memory card.

Advantages:
•Multi-channel – one data logger is sufficient for all working data receiving from the controlled device (15 channel);
•Versatility/Modular – additional modules can be connected to the data logger which makes it possible to expand the range of incoming signals (voltage, current, temperature, discrete/digital inputs, etc.);
•Galvanic isolation – incoming signals of high voltage and current are galvanically separated from other inputs which ensures easiness of data logger connection;
•High reliability – self-control system and data saving algorithm protect against data loss in case of emergency situations (power supply failure, etc.);
•Servicing convenience – four-lined LCD display with backlight enables to adjust the data logger and monitor its work (the values of recorded incoming signals are shown on the display), the key-board is used for setting, scrolling and control of the data logger;
•Remote monitoring and configuration – if the data logger is installed in a poorly accessible place with Ethernet connection it can simultaneously, with the data recording on the memory card, transmit data to PC/Server. This enables remote monitoring of the object. The more detailed analysis can be made on the basis of the data stored on the memory card. Web-interface enables via PC browser to make a remote configuration of the data logger without installing any other additional programs.

DESIGN

The data logger is constructively made in plastic case intended for fixing on DIN-rack 35 mm, case dimensions (91 x 157 x 57 mm) 9 modules of S type. The case is made of crashworthy, self-extinguishing material.

OPERATION PRINCIPLE

The data logger operation principle is based on the measuring values from all sensors connected to the data

logger inputs, accumulating the data in the data logger internal memory and data recording to the external memory

storage – memory card (SD / MMC).

The data logger is equipped with the inbuilt real time clock which is powered (in case of main power failure)

from inbuilt backup power cell – lithium type battery. The power from the backup supply is sufficient continuous

operation of real time clock during 10 years (at temperature 25 ºC).

Additional Information:

  • Item Code: RPM-416
  • Port of Dispatch: New Delhi, India

Basic technical features:

ItemValue
Nominal operating supply voltage (H), V230 / 240
Performance capacity voltage (H/J               ), V24 – 265
Power-line frequency, Hz45 – 65
Power consumption (from line ~220 V), W, not more6.0
Power consumption (from power source +24 V), W, not more2.2
Period of data recording to the memory card, sec.0,001 – 3600
External memory storage (memory card, optional)SD / MMC
Maximal capacity of external memory card, GB32
Supported file systems of external memory card, FAT12, 16, 32
Minimal size of data file, KB32
Maximal size of data file, MB512
Size of one block of recorded data (20 parameters), byte88
Error of clock run, at temperature 25 ºС, not more, sec / day1
Connection to Ethernet or PC10Base-T / 100Base-T
Modbus TCPyes
Web-interfaceyes
FTPyes
The intent of the deviceDigital indication devices
Nominal working modecontinuous
Protection class rating (case / terminal block)ІР40 / IP20
Protection class from electric shockII
Climatic versionNC3.1 (average and cold zone, indoor)
Pollution levelII
Overvoltage categoryII
Isolation nominal voltage, V450
Nominal impulse withstand voltage, kV2.5
Cross-section area of connection terminals, mm²0.2 – 2.5
Terminal screw, N*m0.4
Weight, kg, not more0.5
Overall dimensions, mm91 х 157 х 56.3
Assembling is designed on standard DIN-rack 35 mm 
Orientation, user-defined 

Inputs characteristics:

ItemValue
Voltage input3 channels
Voltage measuring range, V3 – 450
Voltage measuring error (for a sine signal) upto 300 V ± 1 %           exceed 300 V ± 1.5%
Voltage measuring typeRMS / Instant / Peak
Voltage frequency measuring range, Hz25.00 – 70.00
Voltage frequency measuring error (for sine signal), Hz± 0.05
THDr measuring range0 – 100 %
THDr measuring error (if the signal level more than 14% of the range)± 2 %
Current input4 channels
Current measuring range, A0.05 – 10.00
Current measuring error (for a sine signal)± 1.0 %
Current measuring typeRMS / Instant / Peak
Current sensor typeCT with output 5 A
Supported rating values СТ, A5, 10, 15, 20, 30, 40, 50, 75, 100, 150, 200, 300, 400, 600, 800, 1000, 1500, 2000
Current frequency measuring range, Hz25.00 – 70.00
Current frequency measuring error (for sine signal)± 0.05 %
Overload capability 50 A (not often than once a minute), not more, sec0.3
THDr measuring range0 – 100 %
THDr measuring error (if the signal level more than 14% of the range)± 2 %
*Working power calculation3 channels
Active power measuring range, W30 – 200 000 000
Reactive power measuring rate, VAr30 – 200 000 000
Gross power measuring range, VA30 – 200 000 000
Power factor measuring range, cos φ0.01 – 1.000
Power measuring error (for a sine signal)± 2 %
Maximum value of active energy scaler, kW*h999 999 999
Maximum value of reactive energy scaler, kVАr*h999 999 999
Temperature input2 channels
Temperature sensor typePTC1000 / PT1000
Temperature measuring range for PTC1000, ºСfrom -50.0 to +120.0
Temperature measuring range for PT1000, ºСfrom -50.0 to +250.0
Temperature measuring error± 1.5 °C
Voltage input 0 – 10 V (DC)1 channel
Voltage measuring range, V0.01 – 10.00
Voltage measuring error± 1.0 %
Voltage sensor type0 – 10 V / 2 – 10 V
Current input 0 – 20 mA (DC)1 channel
Current measuring range, mA0 – 20
Current measuring error± 1.0 %
Current sensor type0 – 20 mA / 4 – 20 mA
Digital input (Binary)4 channels
Measuring rangeclosed – opened
Digital signal sensor typeDry contact
Pulse frequency measurement range, Pulse * min1 – 29000
Maximum value of pulse scaler999999999

List of channels with corresponding names of measured values:

  Ch.

Number values

  

1

2345

6

1Voltage RMS, VFrequency, HzTHDr, %Peak +  voltage, VPeak –  voltage, VInstantaneous voltage, V
2Voltage RMS, VFrequency, HzTHDr, %Peak +  voltage, VPeak –  voltage, VInstantaneous voltage, V
3Voltage RMS, VFrequency, HzTHDr, %Peak +  voltage, VPeak –  voltage, VInstantaneous voltage, V
4Current RMS, AFrequency, HzTHDr, %Peak +  current, APeak –  current, AInstantaneous current, A
5Current RMS, AFrequency, HzTHDr, %Peak +  current, APeak –  current, AInstantaneous current, A
6Current RMS, AFrequency, HzTHDr, %Peak +  current, APeak –  current, AInstantaneous current, A
7Current RMS, AFrequency, HzTHDr, %Peak +  current, APeak –  current, AInstantaneous current, A
8Temperature, ºС—–—–—–—–—–
9Temperature, ºС—–—–—–—–—–
10Analog voltage, VUser’s Value—–—–—–—–
11Analog current, mAUser’s Value—–—–—–—–
12Digital inputFrequency, Pulse*minPulse Scaler—–—–—–
13Digital InputFrequency, Pulse*minPulse Scaler—–—–—–
14Digital InputFrequency, Pulse*minPulse Scaler—–—–—–
15Digital inputFrequency, Pulse*minPulse Scaler—–—–—–
16Active power, WReactive power, var

Full

power, VA

Power

factor, cos φ

Active Energy Scaler, kW*hReactive Energy Scaler, kVAr*h
17Active power, WReactive power, var

Full

power, VA

Power

factor, cos φ

Active Energy Scaler, kW*hReactive Energy Scaler, kVAr*h
18Active power, WReactive power, var

Full

power, VA

Power

factor, cos φ

Active Energy Scaler, kW*hReactive Energy Scaler, kVAr*h
19Line voltage AB, VLine voltage BC, VLine voltage CA, VNegative sequence voltage, VPositive sequence voltage, VZero sequence voltage, V
        

Types of parameters and their names:

TypeNameUnit of measurementResolution
0Unknown (parameter not use)
1Voltage RMSV0.1
2Voltage InstantaneousV0.1
3Peak + voltage (positive half wave)V0.1
4Peak – voltage (negative half wave)V0.1
5Current RMSA0.01
6Current InstantaneousA0.01
7Peak + current (positive half wave)A0.01
8Peak – current (negative half wave)A0.01
9FrequencyHz0.01
10THDr%1
11TemperatureºC0.1
12Analog voltage 0-10 VV0.01
13Analog current 0-20 mAmA0.01
14Digital input (ON / OFF)1
15Full powerVA0.1
16Active powerW0.1
17Reactive powerVar0.1
18Power factor (cos φ)0.001
19Active Energy ScalerkW*h0.1
20Reactive Energy ScalerkVAr*h0.1
21User’s Value0.1
22Pulse FrequencyPulse*min0.1
23Pulse Scaler1
24Line voltage ABV0,1
25Line voltage BCV0,1
26Line voltage CAV0,1
27Negative sequence voltageV0,1
28Positive sequence voltageV0,1
29Zero sequence voltageV0,1

RPM-416 meets the requirements of the following:

IEC 60947-1; ІEC 60947-6-2; CISPR 11; IEC 61000-4-2.

Harmful substances, in more than allowed concentration, are not available.