MULTIFUNCTION TIME DELAY RELAY WITH EXTERNAL INPUT REV-120

Product Details:

Voltage (V)220 – 240V AC 50/60 Hz
Number of Poles1 Pole, 1 channel
ApplicationOn delay, Off delay, Cyclic timer, Pulse timer, Star-Delta timer
Current (Amps)6A
Time Range10 selectable time range, 0.1 sec to 10 days
BrandNOVATEK ELECTRO
Contact FormSPDT (2NO + 2NC)
Coil Type1 channel Potential free, SPDT

Multifunction time delay relay REV-120 is a microprocessor based device intended for on/off switching the load in user defined time intervals.

REV-120 can be operated by ten operation modes:

  • on-delay;
  • time delay when energizing;
  • periodic with on-delay;
  • periodic with time delay when energizing;
  • off-delay (when control contact opening);
  • pulse I (when control contact closing);
  • pulse II (when control contact opening);
  • on/off delay (according to control contact);
  • pitch of the load relay (during each control contact closing);
  • pulse generator of 0.5 s;
  • selectable time range from 0.1 s to 1 hour.

Additional Information:

  • Item Code: REV-120
  • Port of Dispatch: New Delhi, India

Basic Specifications:

DescriptionValue
Operating supply voltage, V230/240 V
Frequency of supply mains, Hz45 – 62
Voltage at which service capability is maintained, V130-300
Permissible harmonic configuration (unsinusoidality) of power supply voltageEN 50160
Readiness time when energizing, s, no more than0.4
Accuracy of time delay, %, no less than0.5
Accuracy of time setting (accuracy of scale), %, no less than2.5
Number of operation modes10
Adjustment range of time is divided into 10 subranges

0.1 … 1 s

1 … 10 s

6 s … 1 min

1 … 10 min

6 min … 1 h

1 … 10 h

0.1 … 1 day

1 … 10 day

Continuously ON

Continuously OFF

Time delay adjustmentsmooth
Service of the productSwitchgear and control gear
Rated operating conditionContinuous
Type and quantity of contacts (switching)2
Climatic design versionCN 3.1
Protection rating of caseІР40
Protection rating of terminal boxІР20

Commutation lifetime of output contacts if cosj=1:

– under load of 6 А, time, no less than

– under load of 1 А, time, no less than

100,000

1,000,000

Power consumption (under load), W, no more than0.5
Permissible contamination levelII
Overvoltage categoryII
Electric shock protection classII
Rated insulation voltage, V450
Rated impulse withstand voltage, kV2.5
Wire cross-section for connection to terminals, mm²0.5-2
Tightening torque of terminal screws, N*m0.4
Weight, kg, not more0.150
Overall dimensions, H x D x L, mm90 x 65 x 18
Product installation (mounting) is on standard 35mm DIN rail
The product remains functional at any position in space
Case material is self-extinguishing plastic

Specifications of output contacts of the load relay:

сos ф

Max. current at U~250 V, АMax. switching power, VAMax. permissible continuous AC voltage, VMax. current at UDC=28 V, A

1

615002503

Time intervals:

∆T knob position

Time interval∆T knob positionTime interval

1 s

from 0.1 to 1 s10 hfrom 1 to 10 h

10 s

from 1 to 10 s1 dfrom 0.1 to 1 day
1 mfrom 6 s to 1 min10 d

from 1 to 10 days

10 m

from 1 to 10 minON

Continuously ON

1 hfrom 6 min to 1 hOFF

Continuously OFF

The product meets the requirements of the following:

  • Low-voltage switchgear; Part 1; General rules (IEC 60947-1);
  • Low-voltage circuit breaker and controller; Part 6-2; multifunctional equipment; Control and safety switching equipment (ІEC 60947-6-2);
  • Electromagnetic compatibility; Industrial, scientific and medical RF equipment; electromagnetic interference characteristics; standards and measuring procedure (CISPR 11);
  • Electromagnetic compatibility; Part 4-2; Testing and measurement techniques; Electrostatic discharge immunity test (IEC 61000-4-2).

Harmful substances in amounts exceeding maximum permissible concentrations are not available.