AUTOMATIC ELECTRONIC PHASE SELECTOR PEF-320
Product Details:
Voltage Type | AC |
Voltage (V) | 220 – 240 |
Logic | 3 Phase input and Single (best) phase output |
Application | Healthy phase selection, Uninterrupted power supply to load |
Current (Amps) | 16A maximum |
Brand | NOVATEK ELECTRO |
Contact Form | 3 x SPDT Relays |
Switching | Under voltage, Over voltage, Phase loss, Priority phase |
PEF-320 universal automatic electronic phase switch is designed to supply an industrial and domestic single phase 230 V, 50 Hz load from three-phase four-wire mains 3х400+N in order to maintain uninterrupted power supply of essential single-phase loads and protect them against unallowable voltage variations in the mains.
According to the voltage presence and voltage quality on the phases, the PEF-320 will automatically select the optimum phase in limits range set by user and switch the single phase load supply to this phase. It is possible to connect to one of the phases of the electric generator and inverter. The maximum and minimum voltage limits are set by user.
TECHNICAL SPECIFICATIONS
Nominal phase voltage, V 230
Operating capability voltage, on single phase, V 120
Mains frequency, Hz 45 – 55
Trip threshold for Umin, V 160 – 210
Trip threshold for Umax, V 230 – 280
Time delay range for return to the priority phase (Tr), sec * 5 – 200
Time delay range of reclosing (Ton), sec 1 – 600
Fixed time delay of switching over (switching off) for Umin, sec 12
Time of switching over to reserve phases, sec, not more 0.2
Hysteresis (reset coefficient) on voltage, V 5 – 6
Accuracy of threshold trip, V ±3
Maximum switched current (cos φ=1) of additional relay output contacts, A 16
Maximum switched current (cos φ=0.4) of additional relay output contacts, A 5
Device operating capability phase voltage, V 400
Short time allowable operating capability maximal phase voltage, V 450
Power consumption (under load), W, not more than 1.2
Protection degree of the front panel IP 40
Protection degree of terminals block IP 20
Climatic version NF 3.1
Electric shock protection class II
Pollution rate II
Category of overload II
Device scope Control and distribution device
Construction type (installation) On standard DIN-rail, 35 mm
Cross-section of connection terminal wires, mm2
0.5 – 1.5
Screw torque of terminal clams, N*m 0.4
Service life of output contacts:
– under load 16 A, operations, not less than 50000
– under load 5 A, operations, not less than 100000
Overall dimensions H*B*L, mm 90.2*36*64.5
Weight, kg, not more than 0.15
The device remains operational capability in any position in space
Housing material – self-extinguishing plastic
* – If knob Тr is in position “” there is no return to the priority phase