SINGLE PHASE VOLTAGE MONITORING RELAY RN-111M
Product Details:
Voltage Type | AC |
Voltage (V) | 220 – 240 |
Number of Poles | 2 Pole |
Application | Single Phase Voltage Monitoring |
Current (Amps) | 16A |
Brand | NOVATEK ELECTRO |
Contact Form | SPDT (1NO + 1NC) |
Type | Under voltage, Over voltage, Neutral break protection |
RN-111M single phase voltage monitoring relay is designed to de-energize an industrial/appliance single phase 220 – 240V/50Hz load in case of inadmissible voltage variations in the mains with subsequent automatic re-energizing after the circuit parameters recovery. Load is connected to the relay either directly via relay terminals or through a magnetic contactor, depending on the wattage.
The relay can operate in four independent modes:
- Maximum and Minimum Voltage monitoring relay
- Minimum voltage monitoring relay
- Maximum voltage monitoring relay
- Time relay with a restart delay
The device front panel features load status indicator (on/off) and three-digit, seven-segment display, which displays (depending on the device status):
- Actual RMS voltage
- Accurate value of the set-up parameter
- Time remaining till automatic load re-energizing
- Emergency de-energizing the load (RMS voltage flashing)
The variable pot knobs on the front panel allow for setting:
- The maximum allowable voltage tripping threshold
- The minimum allowable voltage tripping threshold
- Time delay for load re-energizing after the circuit parameters recoveryest
Additional Information:
- Item Code: RN-111M
- Port of Dispatch: New Delhi, India
Main Technical Specifications
Rated voltage, V | 220-240 |
Rated voltage frequency, Hz | 47 – 65 |
Harmonical configuration (nonsinusoidality) of power supply voltage | EN 50160 |
Adjustment ranges: – minimal voltage tripping range (Umin), V – maximal voltage tripping range (Umax), V – autoreclosing time delay (Ton), sec | 160 – 230 240 – 280 5 –900 |
Fixed tripping time delay in case maximal voltage fault (Umax) detected, sec | 1 |
Fixed tripping time delay in case minimal voltage fault (Umin) detected, sec | 12 |
Fixed tripping time delay in case of voltage decrease more than 60V than the adjusted minimal voltage tripping threshold (Umin), sec | 0.2 |
Fixed tripping time delay in case of voltage increase more than 30V than the adjusted maximal voltage tripping threshold (Umax), sec | 0.12 |
Maximal commutation current (active power load), A | 16 |
Tripping Voltage level accuracy, V | up to 3 |
Minimal operation voltage level at which RN-111M will keep working, V | 100 |
Maximal operation voltage level at which RN-111M will keep working, V | 420 |
Voltage hysteresis, V | 4 – 5 |
Rower consumption (when de-energization load), W | to 3.5 |
Commutation life of the output contacts: – under 16A power load, times (no less than) – under 5A power load, times (no less than) | 100 000 1 000 000 |
Outer dimensions, (2 S-modules), | Fiqure 1 |
Weight, kg, no less than | 0.10 |
Casing material – self-extinguishing plastic | |
The device preserves functionality in any position within the space |
Parameters of the integrated relay output terminals
| Maximal current at ~ 250V AC | Maximal power when contacts are closed | Maximal commutation power | Maximal allowed AC/DC Voltage | Maximal current at 30V DC |
Cos ф = 0.4 Cos ф = 1 | 5 А 16A | 5000 VA | 4000 VA | 380/150 V | 5 А |
No harmful substances in excess of the maximum permissible concentration is available.
RN-111M complies with requirements: