SINGLE PHASE APPLIANCE PROTECTION RELAY RN-116
Product Details:
Voltage Type | AC |
Voltage (V) | 220 – 240 |
Number of Poles | 2 Pole |
Application | Single Phase Voltage Monitoring (AC, Fridge, TV, Washing Machine, etc.) |
Current (Amps) | 16A |
Brand | NOVATEK ELECTRO |
Contact Form | SPDT (Plug – Socket type) |
Type | Under voltage, Over voltage, Neutral break protection |
Voltage Relay RN-116 is designed for turning off the 220 – 240V AC, 50 Hz residential and industrial single phase load with power of up to 3.5 kW (up to 16 A) at unallowable circuit voltage fluctuation with automatic reset (hereinafter referred to as AR) after circuit parameter recovery.
RN-116 indicates actual input voltage value, fault condition and output relay condition.
Additional Information:
- Item Code: RN-116
- Port of Dispatch: New Delhi
TECHNICAL BRIEF
Rated voltage, V | 220 – 240 |
Rated voltage frequency, Hz | 47 – 65 |
Harmonical configuration (nonsinusoidality) of power supply voltage | EN 61000-3-2 |
Protection degree apparatus | IP30 |
Protection class against electric shock | I |
Permissible contamination level | II |
Overvoltage category | II |
Adjustment ranges: – minimal voltage tripping range (Umin), V – maximal voltage tripping range (Umax), V – autoreclosing time delay (Ton), sec | 160 – 220 230 – 280 5 –900 |
Fixed tripping time delay in case maximal voltage fault (Umax) detected, sec | 1 |
Fixed tripping time delay in case minimal voltage fault (Umin) detected, sec | 7 |
Fixed tripping time delay in case of voltage decrease more than 60V than the adjusted minimal voltage tripping threshold (Umin) or at voltage reduction to less than 145 V, sec | 0.12 |
Fixed tripping time delay in case of voltage increase more than 30V than the adjusted maximal voltage tripping threshold (Umax) or at voltage of over 285 V, sec | 0.12 |
Fixed tripping time at pulsed voltage build-up to over 420 V at pulse duration of over 1.5 msec, sec, not more | 0.02 |
Maximal commutation current (active power load), A (no less than) | 16 |
U tripping threshold determination accuracy, V | up to 3 |
Minimal operation voltage level at which RN-116 will keep working (present value), V Maximal operation voltage level at which RN-116 will keep working (present value), V | 120 400 |
Rated voltage of insulation, V | 4 450 |
Voltage hysteresis, V (no less than) | 4 |
Operational temperature range, °С | from -20 to + 45 |
Storage temperature, °С | from -45 to + 60 |
Total power consumption, mA | up to 15 |
Commutation life of the output contacts: – under 16A power load, times (no less than) – under 5A power load, times (no less than) | 100 000 1 000 000 |
Outer dimensions, (2 S-modules), mm | Figure 1 |
Weight, kg, no less than | 0.160 |
Mounting to standard 35mm DIN rail |
RN-116 “Volt Control” complies with requirements:
IEC 60947-1; ІEC 60947-6-2; CISPR 11; IEC 61000-4-2.
No harmful substances in excess of the maximum permissible concentration is available.