PROGRAMMABLE SEQUENTIAL AND COMBINATION TIMER TK-415
Product Details:
| Voltage Type | AC |
| Voltage (V) | 85 – 270 (50/60 Hz) |
| Number of Channels | 15 Channel |
| Application | Process control, Traffic Light operation, Dust collectors, Conveyor/ Hopper automation |
| Current (Amps) | 10A |
| Brand | NOVATEK ELECTRO |
| Contact Form | 15 x SPDT (potential free NO contacts) |
| Type | Selectable Sequential & Combination modes, PC programming software |
Sequential and Combination Timer with RS-232 communication
Basic functions:
- 15 channel (potential free relay outputs)
- Microprocessor controlled
- Selectable sequential and combination modes in one timer
- Simple change-over between sequential and combination timer
- 7-segment LED indications
- Cascade connection of several devices for extended total number of channels
- Memorization of program after switching off and program operation restart from breakage
- Inputs for timer start and pause control
- Fast resetting
- Copy of settings
- Selectable time range SEC:MSEC, MIN:SEC, HRS:MIN
- RS-232 communication for programming and DCS integration (free PC software provided)
- Program can be executed only one time or/and cyclic operation possible
Timer programming:
Sequential Timer Programming:
- Fix switch RUN/PROG in position PROG
- For sequential timer selection fix switch SEQ/COMB in position SEQ. Supply power to inputs A1 and A2
- Using the button RELAY select the channel 1
- Using the button DLY/ON select time DLY for time setting, during which the contacts of channel relay will be open
- Press RANGE for selection of necessary time range
- Using arrow button to set the necessary time
- Repeat steps 4 through 6 for status time setting ON, during which the contacts of channel relay will be closed
- Repeat steps 3 through 7 for setting of other channels
Combination Timer Programming:
- Fix switch RUN/PROG in position PROG
- For selection of combination timer fix switch SEQ/COMB in position COMB. Energize the inputs A1 and A2
- Using button RELAY select channel 1
- Using button COMBINATION select combination 1
- Using button DLY/ON select time DLY for time setting, during which the contacts of channel relay will be open
- Press RANGE for selection of necessary time range
- Using arrow buttons set the necessary time
- Repeat steps 5 through 7 for set of status ON, during which contacts of channel relay will be closed
- Repeat steps 4 through 8 for setting the other channel combinations
- Repeat steps 3 through 9 for setting of other channels and their combinations
Additional Information:
- Item Code: TK-415
- Port of Dispatch: New Delhi, India
Technical Brief:
| Supply voltage, V | from 85 to 270 AC/DC |
| Frequency range, Hz | 47-63 |
| Power consumption, VA | 8 |
| Time setting range | from 0.1s to 99 hr 59 min |
| Commutation accuracy | ±0.1% + 20ms |
| Number of channels | 15 |
| Number of combinations per channel (ON/OFF) | 8 |
| Operating temperature range, °C | from -25 through +55 |
| Storage temperature, °С | from -35 through +60 |
| Humidity (non condensing) | 85% / 40°С |
| Insulation resistance | >100 МOhm / 500V DC |
| Dimensions, mm | 85.8 х 156.2 х 56.8 |
| Weight, kg | 0.5 |
| Indication of load relay | Yes |
| Protection level | ІР20 |
| Climatic resistance version | NF3.1 |
| Permissible contamination level | || |
| Overvoltage category | || |
| Nominal voltage of isolation, V | 450 |
| Nominal impulse withstanding voltage, kV | 2,5 |
| Cross section of wires of connection terminals, mm² | 0,5-2,5 |
| Maximal tightening torque of terminals external screws, N*m | 0,4 |
| Data memory, years, minimum | 10 |
| Channel contacts type | normally open contact (NO) |
| Mounting | onto standard 35 mm DIN-rail |
| Mounting position | any |
Characteristics of output channels | |||
сos ф | Maximum current at U~250V | Maximum capacity | Maximum current at Uconst=24V |
1.0 | 10 A | 2500 VA | 10 A |
| 0.4 | 4 A | 1000 VA |
|
Commutation resource of output contacts: – mechanical resource – electric resource 10A 250V AC, times, minimum – electric resource 10A 24V DC, times, minimum – electric resource 4A 250V AC (сos j = 0,4 ), times, minimum | 107 100 000 30 000 100 000 | ||
| Signal «Start» | Contact Closure S1 and S2 minimum at 150 milliseconds | ||