DIGITAL PID TEMPERATURE CONTROLLER TR-101
Product Details:
| Current | 10 A |
| Certifications | CE |
| Control Type | PID |
| Brand | NOVATEK ELECTRO |
| Voltage | 24 to 260V AC/DC |
| Controller Type | Proportional-Integral-Diffrential, On/Off Control, PID |
| Number of Channels | 4 Independent Channels |
| Input Sensor | RTD Type |
| Usage | Laboratory, Industrial, Agricultural and Poultry |
| Power | 100 to 240 VAC, 24 VDC |
| Temperature Range | -50 to +200C |
| Communication | RS-485 Modbus RTU/ASCII |
| Model Number | TR-101 |
TR-101 digital temperature controller is used to measure and control device temperature via four independent sensors connected in a two or three-wire circuit, with subsequent indication of the temperature on the display. The device can be used in different industrial, utility and agricultural applications.
The device has the following functions:
- Measuring the temperature on four independent channels using standard sensors
- Regulating the temperature using the proportionate-integral-differential (PID) principle with an output key unit (relay)
- Two-level temperature regulation
- Displaying the currently measured temperature value on the integrated LED digital indicator (scanning)
- Transmitting the measured temperature values of the controlled sensors to a computer via built-in RS-485 Modbus RTU protocol
- Discovering line breakdown or faults in connected sensors
- Digital filtering and correcting of the temperature being measured
- Programming via the front panel buttons or a PC (free PC software)
- Saving the settings in case of power outage
- Protecting the settings against unauthorized changes (password protected)
- TR-101 can use any voltage between 24 and 260V AC, regardless of the polarity
Additional Information:
- Item Code: TR-101
- Port of Dispatch: New Delhi, India
Technical brief and operating conditions:
| Supply voltage, V | 24 – 260 AC/DC |
| Recommended fuse, A | 1 |
| Type of temperature measurement sensors | Pt50, Pt100, Pt500, Pt1000, Cu50, Cu100, Ni100, Ni120, Ni500, Ni1000, PTC1000 |
| Quantity of sensors connectable, pcs | 1 – 4 |
| Sensors wiring schematic | 2 / 3 wires |
| Sensor wire length, depending on the wiring schematic, m | 2- wire, up to 5 3- wire, up to 100 |
| Quantity of output relays, pcs | 4 |
| Data memory, years, no less than | 10 |
| Temperature measurement error, °C | ± 2 |
| Measured temperature range, °C | from -50 to +200 |
| Output relay testing | available |
| RS-485 MODBUS RTU | available |
| PID regulation with keyword (relay) | available |
| Two-position regulator | available |
| Channel measurement time, sec, no more than | 0,6 |
Protection degree: – enclosure – terminal block | ІР30 ІР20 |
| Power consumption (under load), no more than, VA | 4,0 |
| Weight, not more, kg | 0,370 |
| Dimensions, mm | 90 х 139 х 63 |
Output contacts commutation lifetime: – electrical life 10А, 250V AC, times, no less than – electrical life 10А, 24V DC, times, no less than | 100 thousand 100 thousand |
| Mounting onto standard 35 mm DIN-rail | |
| Mounting position any | |
Output contacts specification:
Cos Ф | Max. current at ~ 250 V AC | Maximum power | Max. voltage ~ | Max. current for U = 30V D.C. |
| 1.0 | 10 А | 4000 VА | 440 V | 3 А |
TR-101 complies with requirements of:
IEC 60947-1:2004, ІDТ; ІEC 60947-6-2:1992, ІDT; CISPR 11:2004, IDT; IEC 61000-4-2:2001, IDT
No harmful substances in excess of the maximum permissible concentration is available.